TECHNICAL SPECIFICATIONS
GENERAL DESCRIPTION:
Built in 2000, 70 Hudson Street is a 433,197 RSF, 12 story state of the art office building.
CONSTRUCTION DETAILS:
Foundation:
Reinforced concrete slab set on steel piles.
Frame:
Concrete slab on rolled structural steel beams and columns.
Exterior Finish:
Glass curtain wall with granite base. Precast concrete with punched windows.
Lobby Finishes:
Limestone walls & columns. Marble polished finished floors.Limestone polished finished borders & accents. Marble countertops at concierge desk.
Slab Flooring:
Recessed 8”
FLOOR CAPACITY:
Typical Ceiling Heights:
Slab - to - slab height is 13’- 3”.
Finished ceiling heights are typically 9’- 0” and greater.
Window Mullion Spacing:
East / West: 4’-10” to 5’- 0”
North / South: 4’-7” to 4’- 8 ½”
Column Spacing:
East / West: 28’- 6” at the corners and 28’- 0” in between.
North / South: 27’- 6” at the corners and 27’- 0” in between.
Freight Elevators:
Door opening Height 7’11” / Width 7’2”
Interior - Height 8’ 0” / Width 7’2” / Depth 9’2”
BUILDING DETAILS:
Parking:
226 parking spaces
Telecom Providers:
Verizon and Spectrotel. Landlord will work with tenant to
secure additional providers. Cable television is provided by Comcast.
HEATING, VENTILATION AND AIR CONDITIONING:
System:
The building is served by a roof-top penthouse which
consists of three multiple cell cooling towers with
heat exchanges and pumps to service two, ninety
(90) ton water-cooled AC units on each office floor.
Design Criteria:
Air-conditioning, in summer or winter conditions,
providing not less than 1 CFM per useable square
foot of the Premises at 57ºF, plus or minus 3ºF, at not
less than 1.5 inches (1.5”) external static pressure,
measured at discharge. In the winter, hot water for
VAV Reheating system to provide 70ºF at 10ºF
outside temperature.
Heat:
Heat is provided by three gas fired hot water boilers
and pumps located in the penthouse, to serve hot
water coils in variable volume boxes.
Air Conditioning:
Two ninety (90) ton water-cooled variable volume
units per floor with free cooling coils. Each floor has its own
AC controls and can operate independently
HVAC Operation Hours:
Monday through Friday: 8:00 AM to 6:00 PM
Supplemental Cooling:
720 Tons of Supplemental Condenser Water is
available for Tenant’s supplemental cooling needs
ELECTRICITY:
General:
Electric service to the building is 14,000 max.
amps at 277/480 volt. The service is served by three
(3) 26 KV circuit cables feeding six (6) 277/480 volt
transformers. The south waterfront switching station
consists of two (2) 230 KV to 26 KV station
transformers, supplying a 26 KV “ring” bus at the
station. Each transformer can carry the full load of the
26 KV circuits exiting the station. Bus duct and
switchgear rooms are located at ground level.
Emergency Power:
350 KW generator is for life safety not tenant use;
building has 4 - 800 KW generators on P2 level for tenant use
Substation:
Waterfront Substation located at Grand Street and
Pacific Avenue, Jersey City